Mini PLC Small Relay PR6 Series Programmable Relay XLogic Model with Non-expandable PR-6DC-DA-R
- Model:
- PR-6DC-DA-R
- Brand:
- RIEVTECH
| PR-6 Series CPU | |||||||||
| Model | Expansion | Supply volt | Inputs | Outputs | High-speed count | PWM | HMI | RTC | G . W(G) |
| PR-6AC-R | NO | AC 110~240V | 4 DI | 2 relays(10A) | NO | NO | NO | YES | 180 |
| PR-6DC-DA-R | NO | DC12V-24V |
4 DI(I1-I4) /4(0...10V) |
2 relays(10A) | NO | NO | NO | YES | 180 |
GENERAL SPECIFICATIONS
Timers : 64
Counters : 64
Function Blocks: 64
Operation temp. : -20℃-55℃
Storage:-40℃-70℃
Protection: IP20
RTC accuracy : MAX ±2S/day
RTC time interval : 64
RTC Backup at 25 °C : 20 days
Program and settings Backup :10 years
Data Power-off retentivity : No
Cycle time: typ. 0.6ms to 8.0ms
Dimensions: 48*90*64 (Unit, mm)
Certificate: CE, C-UL, RoSH, REACH
Installation:35mm- DIN rail or screw for installation
Expansion capacity: No
Password protection :4-digit number password protection or disable program upload function
Communication interface : TTL interface , 1 Program/RS232 port
Communication protocol : Modbus RTU/ASCII
Technical Index
| Power supply: | |
| Nominal voltage | DC 12-24V |
| Operating limits | DC 10.8-28.8V |
| Immunity from micro power cuts | Typ.5 ms |
| Max. Startup current | Max. 0.25A |
| Max. absorbed power | 1.1 W (10.8V dc) ; 1.2W (28.8V dc) |
| Protection against polarity inversions | Yes |
| Input parameters: | |
| Input No | 4 ( I1-I4 ) |
| Digital input | 4 ( I1-I4 ) |
| Analogue input | 4 ( I1-I4)(0..10V DC) |
| Inputs used as digital inputs( I1-I4 ) | |
| Input voltage | DC0-28.8V |
| Input signal0 | < 5V DC;<0.1mA |
| Input signal1 | >8 V DC;>0.3mA |
| Input current |
0.4mA @ 10.8V dc 0.5mA @ 12.0 V dc 1.2mA @ 24 V dc 1.5mA @ 28.8 V dc |
| Response time | 0 to 1 :Typ. 1.5 ms ;1 to 0 :Typ. 1.5 ms |
| Maximum counting frequency | Typ.:4 HZ |
| Sensor type | Contact or 3-wire PNP |
| Input type | Resistive |
| Isolation between power supply and inputs | None |
| Isolation between inputs | None |
| Inputs used as analog inputs( I1-I4 ) | |
| Measurement range | DC 0---10V |
| Input impedance | Min, 24KΩ ; Max. 72KΩ |
| Input voltage | 28.8 V DC max |
| Resolution | 9bit ,0.015V |
| Accuracy at 25 °C | ± (Max.0.03)V |
| Accuracy at 55 °C | ± (Max.0.06)V |
| Isolation between analog channel and power supply | None |
| Cable length | 10 m max. shielded and twisted |
| Output parameters: | |
| Output No. | 2 (Q1-Q2) |
| Output type | Relay output |
| Max. Allowable Power Force |
CE: 10A,250V AC/DC30V UL/CUL:10A,250V AC; 5A, DC28V |
| Electrical durability Expectancy | 105 Operations at Rated Resistive Load |
| Mechanical life | 107 Operations at No Load condition |
| Response time |
Operate Time : 15 mSec. Max. Release Time : 10 mSec. Max. |
| Built-in protections |
Against short-circuits: None Against overvoltages and overloads: None |
| Switch frequency: | |
| Mechanism | 10Hz |
| Resistor/light load | 2Hz |
| Sensitive load | 0.5Hz |
| Other parameters: | |
| Weight | Approx.180g |
Installation Dimensions

Wiring Diagram
Input(Digital&Analog 0..10V) & Ouptput(Relay) :